Uneven phase distribution in heat exchangers is a cause of severe reductions in thermal performances of
refrigeration equipment. To date, no general design rules are available to avoid phase separation in manifolds
with several outlet channels, and even predicting the phase and mass distribution in parallel channels
is a demanding task. In the present paper, measurements of two-phase air–water distributions are
reported with reference to a horizontal header supplying 16 vertical upward channels. The effects of
the operating conditions, the header geometry and the inlet port nozzle were investigated in the ranges of liquid and gas superficial velocities of 0.2–1.2 and 1.5–16.5 m/s, respectively. Among the fitting devices used, the insertion of a co-axial, multi-hole distributor inside the header confirmed the possibility of greatly improving the liquid and gas flow distribution by the proper selection of position, diameter and number of the flow openings between the supplying distributor and the system of parallel channels connected to the header.